EPA Wood-Burning FireplaceP/N 850,038M REV. B 02/2007MONTESTMODELMONTECITO ESTATE™ This installation manual will enable you to obtain a safe, effici
1. Combustible material must be installed flush with the fireplace. It may not project in front of and on the fireplace (i.e. the steel facade of the fir
Figure 1713” x 13”10’ Max.10’ Max.Rain CapFlashing CollarFlashingRoof SupportAtticRadiation ShieldNon-CombustibleFlameproofFacing56” Min.68” Min.Figur
OUTSIDE AIR KITIt is mandatory to install an outside air connection to the Montecito Estate™. The following components are required and ar
8. A rain cap must be installed on top of the chimney. Failure to install a rain cap may cause corrosion problems.9. Cut and frame square holes in all
CHIMNEY INSTALLATION INSTRUC-TIONS1. Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see Figure 22). Use a plumb
Roof Down Slope Hole SizeDEGREE OF SLOPE Secure Temp™ S2100+ Nova Temp™ HT6000+ Secure Temp GXACBIRoof Pitch 7” 7”0 * 15” (380 mm) 15” (380 mm)2/12
OFFSET CHIMNEY INSTALLATIONThe minimum chimney height when using elbows is:Chimney ElbowOffset & HeightTwo Lengths Between Elbows8” 12” 18” 24” 36
Figure 28OFFSET CHIMNEY INSTALLATIONRain CapCollarRoof FlashingOffset SupportInsulated WallRadiation ShieldFraming2” x 3”Figure 29Roof SupportNote: In
ANGLED WALL RADIATION SHIELD(XRSMI30 and AC10RSMI30)When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop or wa
INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATIONWARNING: Before starting the installation, the masonry chimney must be inspected by a qualified chimne
WARNINGTo avoid the risk of damaging fireplace materials and increas-ing the risk of fire, do not use the fireplace to cook or warm food. WARNI
CHIMNEY - PARTS AND COMPONENTS LISTSSecure Temp GX - 2” Insulated Galvanized Chimney System (Recommended Insulated System)Galvanized (7” ID & 11”
ACBI Chimney*(7” I.D., 13” O.D. AC - Air Cooled) * AC Chimney is NOT recommended at elevations above 4,000 feet or in cold climates (climates where te
CLEARANCE TO COMBUSTIBLESThe following clearances meet the minimum requirements for a safe installation:• Side wall (fireplace front): 24” (4
NOTES23
Printed in Canada © 2006 by LENNOX HEARTH PRODUCTSP/N 850,038M REV. B 02/2007 The manufacturer reserves the right to make changes at any time, wi
TABLE OF CONTENTSSafety Rules ...Page 2 Introduction ...Page 3Parts Required
The combustion air control should be opened before opening the doors to minimize the possi-bility of back draft coming into the room (Figure 1-A) More
The unit will burn best with 2-3 pieces of cord wood spaced 1 to 2 inches apart and allowing air to get under the fuel. Criss-crossing or ar-ranging
Figure 5IMPORTANT CAUTIONSA. Do not block the hot air vents to the fire-place as this will cause the fireplace to overheat.B. Never use gasoline, k
DOOR INSTALLATIONThe doors must be put in place only when the installation of the Montecito Estate™ is completed. All you have to do is fit the male p
FIREPLACE INSTALLATIONLocating The Montecito Estate™ The best location to install your fireplace is determined by considering the location of windows,
Figure 11 Insulated Chase Construction7 Ft. Min.Attic RadiationShieldRoof SupportStorm CollarFlashingDrywall or Any Rigid Material 2” x 4”1/2” Plywood